This instruction show you guide on how to solve Doosan Bobcat fault code P203A DEF level sensor open circuit.
Preparations:
2026 Doosan Data Monitoring System DMS-5
2025 Doosan Diagnostic Software Full Package
1 Overview
E SPNFMI:E00353203
Reason:
1 Electrical problem (DEF level sensor, Wiring harness in the DEF module)
2 Electrical problem (CAN wiring harness-insulation,Resistance)
Effect:Inducement Group5 (Tampering)
The pin definition is dependent on the DEF tank type.
No Description
1 Battery +12V
2 Ground
3 CAN Low
4 CAN High
2) Component Location
DEF tank location and connector is dependent on machine application.

3) Condition for Running Diagnostic
Continuously checked in every sample time when there is no bus-off and no timeout error
4 Condition for Setting the Fault Code
The error is reported if its FMI is equal to 3 (Open circuit)
5 Condition for Clearing the Fault Code
The error is healed when its FMI is not equal to 3
6 Check List